|
Testing. Fault Loop Impedance.
Fault loop impedance testing must be carried out as part of any electrical
work that involves the connecting of a appliance or outlet to a circuit to
guarantee the Electrical safety of a circuit.
AS/NZS 3000 Wiring Rules applies throughout Australia and New Zealand and is
referenced in whole or in part in legislation in all states of Australia and in
New Zealand, as a minimum requirement.
To that extent, the electrical circuit design and electrical installation of
these circuits must meet the requirements of the Wiring Rules standard.
One of the basic safety requirements stated in AS/NZS 3000 Wiring Rules is
protection from 'indirect contact' with live parts.
Automatic disconnection of the power supply is the most common method of
achieving this.
To comply with Clause 1.7.4.3.3 of AS/NZS 3000 Wiring Rules, each circuit in
an electrical installation must be designed and protected so that automatic
disconnection of the power supply will occur within the specified time when a
short circuit of negligible impedance occurs between an active conductor or an
exposed conductive part anywhere in an electrical installation.
To fulfil this requirement of AS/NZS 3000 Wiring Rules when a fault current
flows, the impedance of the fault current path (referred to in AS/NZS 3000
Wiring Rules as the Fault Loop Impedance Path) must be low enough to
allow sufficient current to flow to cause the protective device to operate
within the specified time.
Understanding Loop
Impedance and Why it is Important
Measuring or calculating loop impedance is essential
when determining the prospective short circuit current in a circuit so that the
correct overload protection is used.
A fundamental question must be answered “WILL THE
PROTECTION DEVICE FUNCTION DURING A FAULT CONDITION?”
To
determine the fault current rating for an overload device the maximum current
that can be delivered to that point must be considered. Loop impedance at that
point and the previous protective device will determine the correct rating.
In a
short circuit the overload device must be able to withstand that current before
tripping. In other words the protection device must not melt , the contacts must
not weld together while the fault is present and the device must be capable of
opening under fault conditions.
Prospective short circuit current measured in an
installation is used to consider whether the circuit is capable of carrying
sufficient current so as to trip the overload device in the specified time.
Loop
impedances can be calculated as per appendix B of the Wiring Rules or measured
with a suitable test instrument. Using a test instrument may give you a more
accurate reading of the circuit because it will include all factors in the line
such as bad connections and back e.m.f.s generated by adjacent electrical lines
and other loads being present on the system at the time of the test Note that
impedance on the active and neutral lines are dynamic due to other sub circuits
attached to that line and their changes. The earth impedance without the MEN
connection would be constant.
Using the loop impedance values, the tripping time of circuit breakers or fuses
in the circuit can be determined. Clause 1.7.4.3.4 of the wiring rules states
the required maximum times for circuit disconnection.
Using a loop impedance meter is useful in determining if the breaker can carry
the load during the time it takes to open the circuit and determine the time the
overload device could take to open. Using a loop impedance meter is optional
according to the wiring rules. However its use is essential for testing
installations and will improve confidence and safety in ensuring that overload
protection will operate correctly. It is also very useful in fault finding such
as locating loose connections.
Your Electrical Contractor must have the tools to test and
record your fault loop impedance for all circuits worked on.
You don't need to know how or why but as the owner you need to be aware the
Electrician has completed these tests.
IN BASIC
ENGLISH:
If your
appliance becomes faulty, The resistance in the
earth
return circuit must
be low enough to allow the Circuit Breaker or fuse to trip (due to a high power
usage) before the voltage can rise above the 50 Volt on the outer or metal shell
or parts and ground or surrounding materials. This will help so you are
protected from being electrocuted if you touch the faulty unit.
(This
requirement and the installation of a Safety Switch will provide a high level of
personal Safety). Failure to do this test and not having the correct setup will
create a very dangerous situation.
|